TEXECOM Premier alarm panel connections and configuration
88/168/640
The panel software version must be 6.x or above.
Connect the WebWay panel interface (TTL) R, T and RTN using the supplied molex cable. This goes T- red R-Green
RTN-Blue and it plugs onto Com port 1.
Connect the WebWay PWR + and - to any relevant Power and Ground terminals.
The texecom panel configuration is uploaded via the Wintex software and downloaded to the panel on com port 2 from a
local PC.
The only thing to configure in the panel is enabling upload/download if required
Key settings in the communications menu are:
In Options:
Enable communicator must be ticked
UDL passcode (set in the panel) must match.
Dial attempts 1, ring before answer 3
In ARC’s:
Account number (site ID)
SIA Level 2/3
Connect Via IP - ticked
Send SIA text - ticked
In Radio-Pad and Com Port options:
Com Port 1 WebWayOne module
Local IP address 127.0.0.1
Local IP port 50561
Gateway 127.0.0.1
Subnet Mask 255.255.255.0
Name/SMG port 50561